For every breaker with an adjustable trip unit, record the trip unit model, the sensor or rating plug, and each setting: long-time pickup and delay, short-time pickup and delay, instantaneous, and ground fault. Take a clear photo of the dials or settings screen as proof.
What to record
| Setting | What it is |
|---|---|
| Rating plug / sensor | The base rating the other settings multiply from |
| Long-time (L) | Pickup (often a multiple of the plug) and delay band |
| Short-time (S) | Pickup and delay, sometimes with an I²t on/off option |
| Instantaneous (I) | Pickup, often a multiple of the plug or pickup |
| Ground fault (G) | Pickup and delay, if the unit has it |
Also note the trip unit model and firmware or style, because the same dial position can mean different values on different units.
Where to find them
- Analog trip units: rotary dials on the front of the breaker, usually behind a clear cover.
- Digital trip units: a display or menu. Step through every settings page and photograph each one.
- Thermal-magnetic breakers: usually fixed trip, sometimes an adjustable instantaneous dial. Record the rating and any dial.
Tips that save a return trip
- Photograph the whole trip unit, not just one dial, so nothing has to be remembered.
- Write down the breaker's position or name with each photo.
- If a setting can't be read, mark it as unknown instead of guessing.
- Compare against the last study: changed settings are common and important.
Safety
Reading trip units may require opening equipment that is energized. That is work for qualified persons with the PPE and procedures your NFPA 70E program requires.