Under NFPA 70E, an arc flash label must show the nominal system voltage, the arc flash boundary, and at least one of: the available incident energy with its working distance, or the arc flash PPE category (not both), the minimum arc rating of clothing, or the site-specific level of PPE.
What the label shows
| Item | Notes |
|---|---|
| Nominal system voltage | Always required |
| Arc flash boundary | Always required |
| Incident energy + working distance, or PPE category | One of the allowed options (show one, not both) |
| Minimum arc rating of clothing | One of the allowed options |
| Site-specific level of PPE | One of the allowed options |
Many facilities also show the equipment name, the date of the assessment and who performed it, which makes audits and updates easier.
When labels must be updated
- When the arc flash risk assessment is reviewed or updated, at intervals not exceeding five years under NFPA 70E
- When major modifications or renovations change the system, such as new equipment, a new utility transformer or changed protective device settings
- When a label is damaged or unreadable
Why labels go wrong
Labels are only as accurate as the study, and the study is only as accurate as the field data. Changed trip settings or equipment that was never added to the model are the usual causes.